- 9010/9020 LCD
- ATEX 94/9/EC compatible where applicable
- Failure status for low AC/DC power
- Over range EEEE latching
- Series connected opto-isolators provide failure status
- Redundant dual contact failure relay [select able latching/non-latching function]
- Alarm threshold inhibit
- Choice of measuring units–LEL-LELm-PPM-% Vol-g/m3 or blank
- Operates with a complete range of gas sensors and transmitters including semiconductor sensors, conventional smoke and temperature sensors, manual call points, thermo-resistive cable
- 4–20mA current loop accept [one person]
- Full internal diagnostics
- User-friendly configurable operation
- Firmware can be easily loaded via laptop
- Versatile system functions with logic levels
- Adjustments via membrane keypads
- Up to 20 channels per rack
- Individual terminal blocks per module
- Meets ATEX Directive 94/9/EC requirements
- A multi-purpose version which accepts both bridge [mV] and active [4 – 20 mA] input signals
- A cost-effective version operating on a4–20mA input signal is also available
- Satisfies a variety of gas monitoring applications/industries
- Inherent reliability minimises spurious alarms and unexpected “down-time”
- No tools required for adjustments [operation by Access Code]
- High density monitoring
- 9020-4 LCD
- ATEX 94/9/EC and MED 96/98/EC approved
- 4-digit, 7-segment back lit Liquid Crystal Display – one for each measuring channel
- High-brightness alarm LED’s on front door
- Choice of measuring Units – LEL, LELm, PPM, %Vol, g/m3 or blank
- Redundant dual contact failure relay with safety function
- Alarm threshold inhibit
- User-friendly software configuration by specific Access Codes
- Each Channel has three alarm thresholds: Caution, Alarm, Warning
- Analogue output signal for each channel with linearisation
- RS-485 common serial interface ModBUS RTU data transmission
- 4 –20 mA current loop calibration at Transmitter only [one person]
- Full internal diagnostics
- Versatile system functions with logic levels
- Common alarm, horn and failure relay contacts available on terminal board
- Sheet metal vibration-proof IP 65 enclosure with bottom gland plate for cable entry